Subfloor & prep · Calculator

Radiant Floor Heating Calculator

Enter the room, the area under fixtures, the gap the system needs from walls and fixtures, the heat output and the voltage, and this calculator returns the heated area, the size of mat or cable kit to buy, the watts and amps, and the circuit size with the continuous-load rule applied.

Electric floor heat is sized by the open floor, not the room. Heating cable cannot go under a vanity, a tub or a toilet, it stays a few inches from the walls, and it cannot be cut, so the kit must be no bigger than the space it goes in. This calculator subtracts what the cable cannot go under, gives the heated area to match a kit against, and turns it into the load and the circuit an electrician will need.

Radiant Floor Heating Calculator

Units
ft
ft
sq ft

Vanity, tub, shower base, toilet, cabinets, island: heat cable never goes under them

in

Makers ask for about 3 to 6 in (8 to 15 cm) from walls and 4 in from a toilet flange

W per sq ft

Mats and cables are 10 to 15 W per sq ft (110 to 160 W/m²); 12 W per sq ft is typical

Supply voltage
in

Mats are 18 to 36 in wide (50 cm in metric); leave the default for cable kits

Example result for the starting values. Enter your own and press Calculate.

Heated area

20 sq ft

237 W, 1.98 A at 120 V, 15 A circuit

Heater size
237 W
Current
1.98 A
Circuit
15 A
Heated area, load and circuit
Room40 sq ft
Heated area20 sq ft
Share of the room heated49%
Heater size237 W
Current draw1.98 A at 120 V
Circuit (125% of the load)15 A
Mat length at this width (about)11.9 ft
Show the arithmetic
  1. Room = 8 ft × 5 ft = 40 sq ft
  2. Inside the 4 in wall gap = 32 sq ft; less fixtures 12 sq ft = 20 sq ft heated
  3. Power = 20 sq ft × 12 W per sq ft = 237 W
  4. Current = 237 W ÷ 120 V = 1.98 A; × 1.25 for a continuous load = 2.47 A → 15 A circuit
  5. Mat length ≈ 20 sq ft ÷ 20 in = 11.9 ft
  • Choose the mat or cable kit whose heated area is the size just below the figure here, never above: heat cable cannot be cut, and a mat that is too big ends up under a fixture. The maker's layout tool gives the exact kit.
  • Electric floor heat needs a GFCI-protected circuit (NEC 424.44) and a floor-sensing thermostat. In most places the connection must be made by a licensed electrician; check the inspection rules where you live.
  • Less than half the room is heated. That is normal in a small bathroom, but the room may still need another heat source; floor heat is usually sold for comfort, not as the room's only heating.

Shopping list

  • 1 floor heating mat or cable kit covering about 20 sq ft (the next size down), 120 V
  • 1 floor-sensing thermostat with GFCI (often in the kit)
  • 1 roll uncoupling or decoupling membrane, or thinset, as the system specifies

Understanding your result

The headline is the heated area, with the watts, amps and circuit beneath it. The stats repeat the heater size, the current and the circuit; the table gives the room, the heated area and its share of the room, the heater size, the current, the circuit and the approximate length of a mat of the width you entered.

Heated area is the room less the margin at the walls and less the area under fixtures. The margin is taken off all four walls; the fixtures are taken off in total. The result is the open floor, the part people actually stand on, and it is the figure to match against a kit: choose the kit whose heated area is the size just below this figure, never above, because cable cannot be cut.

Heater size is that area times the output per square foot, and the current is the watts divided by the voltage. The circuit applies the 125% continuous-load rule: the circuit must carry 1.25 times the heater current, so a 15 A circuit takes up to 12 A of heater. For what the heat costs to run, use the radiant floor running cost calculator with the watts from here; for the tile that goes on top, the floor tile calculator, and for the mortar over the mat, the thinset calculator, since mats embedded in thinset use more of it.

How we calculate this

inside margin = (length − 2 × gap) × (width − 2 × gap) heated area = inside margin − area under fixtures watts = heated area × W per sq ft amps = watts ÷ volts circuit = 15 A if amps × 1.25 ≤ 15, 20 A if ≤ 20, otherwise two circuits or a power module mat length ≈ heated area ÷ mat width

The continuous-load rule is from the National Electrical Code (an electric space-heating load is treated as continuous and its branch circuit sized at 125%), and the GFCI requirement for floor heating cables is in NEC 424.44. Output figures come from the makers of mats and membrane systems; a membrane system at standard spacing gives about 12.7 W per sq ft. The guide to planning electric radiant heat walks through layout and thermostats, and the shower tiling guide covers heated bathroom floors under tile.

The assumptions behind the numbers

Assumption Default Where it comes from
Output 12 W per sq ft (130 W/m²) Typical mats and cables (10 to 15 W per sq ft); Schluter DITRA-HEAT about 12.7 at standard spacing
Wall gap 4 in (10 cm) Typical maker instructions: 3 to 6 in from walls, 4 in from a toilet flange
Voltage 120 V (230 V metric) Typical US bathroom circuit; larger floors use 240 V
Circuit sizing 125% of the load NEC continuous-load rule for space heating
GFCI required NEC 424.44
Thermostat limit 15 A Typical floor-heat thermostats; larger loads use a relay or power module

Assumptions last reviewed October 8, 2026.

The calculator handles electric mats and cables only; hydronic floors with water pipes are sized by a heating designer. It does not design the circuit, choose the wire gauge or check the panel’s capacity, which is the electrician’s job. It does not account for heat lost into an uninsulated slab, which can halve the warmth felt; insulating board under the heater fixes that. And it treats the fixtures as one total area, so a complicated bathroom is best checked against the maker’s free layout service.

Two worked examples

A 9 × 7 ft bathroom

18 sq ft under the vanity, toilet and tub edge, 4 in margin, 12 W per sq ft, 120 V, 20 in mat.

  • Inside the margin: 8.33 × 6.33 = 53 sq ft; less 18 sq ft fixtures = 35 sq ft heated
  • Heater: 35 × 12 = 417 W; current 417 ÷ 120 = 3.5 A
  • Circuit: 3.5 × 1.25 = 4.3 A, a 15 A circuit; mat about 21 ft long at 20 in wide

Just over half the room is heated, which is normal in a bathroom; the heat is where the feet are. A 35 sq ft kit is too big if your measurements are generous; choose the size below.

A 16 × 12 ft kitchen at 240 V

48 sq ft under the cabinets and island.

  • Inside the margin: 15.33 × 11.33 = 174 sq ft; less 48 = 126 sq ft heated
  • Heater: 126 × 12 = 1,509 W; current at 240 V = 6.3 A
  • Circuit: 6.3 × 1.25 = 7.9 A, a 15 A circuit

At 120 V the same heater would draw 12.6 A and need a 20 A circuit, which is why kitchens and larger rooms are usually wired at 240 V. The running cost is the same either way; the watts decide it.

Where to find your inputs

Room. Wall to wall at floor level.

Fixtures. The footprint of the vanity, toilet, tub or shower base, cabinets and island, added together.

Wall gap. From the heating system’s installation manual.

Output and voltage. From the kit you are considering; the voltage from the circuit the electrician will provide.

Common mistakes

  • Sizing by the room. Heat goes only where there are no fixtures. Use the open floor.
  • A kit bigger than the space. The cable cannot be cut. Choose the size below.
  • No GFCI. Floor heat in a bathroom must be GFCI-protected.
  • Testing the cable once. Test resistance before, during and after tiling, as the maker says.
  • No insulation under a slab. Much of the heat goes down. Insulate where you can.
  • DIY wiring. The connection is electrician’s work in most places.

Questions people ask

What size radiant heating mat for a bathroom?
Measure the open floor where people stand. A 5 × 8 ft bathroom with about 12 sq ft under the vanity, toilet and tub edge, and a 4 inch gap at the walls, has about 20 sq ft to heat, so a kit of about 20 sq ft at 12 W per sq ft, 240 W, drawing 2 A at 120 V.
How many watts per square foot for floor heating?
Most electric mats and cables deliver 10 to 15 W per sq ft; 12 W is typical for a mat and about 12.7 W for a membrane system at standard cable spacing. More watts per square foot heat faster and cost more to run.
What circuit does electric floor heat need?
A dedicated circuit with GFCI protection, sized at 125% of the heating load because it is a continuous load. Up to about 1,440 W at 120 V fits a 15 A circuit; a larger floor goes to 240 V or a second circuit. Most thermostats switch up to 15 A.
Can I cut a floor heating mat?
You can cut the mesh backing to turn a corner, but never the heating cable itself; cutting it changes its resistance and can cause a fire. That is why the kit must be sized to fit the heated area without trimming the cable.
Does floor heat go under the toilet or vanity?
No. Heating cable must not run under fixtures, cabinets, or a bathtub, where the heat is trapped. Most makers also keep the cable at least 4 inches from a toilet wax ring and a few inches from walls.
Do I need an electrician for radiant floor heat?
The mat can be laid by a careful DIYer, but the connection to the circuit and the thermostat is electrical work that in most places needs a licensed electrician and an inspection. Check the rules where you live.
Embed this calculator on your site

Paste the code into any page. It is free to use; the only thing we ask is that the credit link under the calculator stays.

See all calculators: embed